Energy Storage Systems

Shave the peak. Ride through the outage.

Containerised LFP storage that cuts evening peak demand, carries critical loads through load-shedding and steadies solar output on the grid — sized from your own load data.

LFP containers · liquid-cooled

System size
100 kWh – 50 MWh
Chemistry
LFP
Switchover
< 20 ms
Cycle life
6,000+ cycles

Why storage now

The expensive kilowatts arrive after sunset.

Bangladesh's grid peaks in the evening, exactly when solar stops producing and load-shedding bites hardest. A battery moves cheap energy into those hours.

  • Peak shavingHold demand under your contracted limit through the 17:00–23:00 peak and cut demand-related charges.
  • BackupCritical lines switch to battery in under 20 ms — no genset start gap, no scrapped batch.
  • Grid stabilityFast frequency response, ramp-rate control and firming that let more solar connect to the grid.

Site demand over a weekday, kW

The battery discharges above a 900 kW cap in the evening peak and recharges from 00:00 to 06:00.

  • Demand without storage
  • Demand with 350 kW / 1.4 MWh ESS
05001,0001,50000:0006:0012:0017:0023:00Evening peak
Illustrative 24-hour profile for a knit-composite plant with a 350 kW / 1.4 MWh LFP system. Peak window 17:00–23:00.
Peak demand cut
−280 kW (24%)
Energy shifted
1,030 kWh
Recharge window
00:00–06:00

Use cases

Three jobs a battery does better than a generator.

The same LFP platform, configured by its control logic: shave, back up or support the grid — or stack all three.

Rooftop PV + ESS bay

01

Industrial

Peak shaving for factories

Discharge through the evening peak, hold demand under the contracted limit and pair with rooftop solar to store midday surplus.

20–30%lower peak demand

  • Time-of-use arbitrage
  • Contracted-demand limit control
  • Solar self-consumption
02

Commercial & institutional

Backup for critical loads

Hospitals, data rooms, cold chains and dyeing lines ride through outages on battery instead of waiting for a genset.

< 20 msswitchover to battery

  • Critical-load panel separation
  • Diesel runtime cut
  • Seamless return to grid
03

Utility & IPP

Grid support at scale

MW-scale systems at solar parks and substations for frequency response, ramp-rate control and evening firming.

MW-scalesub-second response

  • Frequency regulation
  • PV ramp-rate smoothing
  • Renewable firming

Battery chemistry

Why every system we build is LFP.

Lithium iron phosphate trades a little energy density for the cycle life, thermal stability and heat tolerance a Bangladeshi plant room actually needs.

Battery chemistry comparison: LFP, NMC and lead-acid
CriteriaOur standardLFPLithium iron phosphateNMCNickel manganese cobaltLead-acidVRLA / flooded
Cycle life (to ~80% capacity)6,000–10,0003,000–5,000500–1,500
Usable depth of discharge90–95%80–90%~50%
Round-trip efficiency92–95%90–95%75–85%
Thermal stabilityHigh · runaway onset ~250 °C+Lower · onset ~150–200 °CStable · hydrogen off-gassing
Energy densityMediumHighLow
Tolerance of 35–40 °C ambientGood with active coolingNeeds tight thermal controlLife falls sharply with heat
Calendar life15–20 years10–15 years3–7 years
Cobalt- and nickel-freeYesNoYes
Lifetime cost per kWh cycledLowestMediumHighest

Typical ranges from manufacturer datasheets at 25 °C and rated C-rate. Actual cycle life depends on depth of discharge, temperature and charge rate.

Sizing guidance

Sized from your meter data, not a rule of thumb.

Power (kW) sets how much load the battery can carry. Energy (kWh) sets for how long. Get either wrong and you pay for capacity you never use.

Energy sizing formula

Pshave
Peak demand above the cap, kW
tpeak
Hours the cap must hold, h
DoD
Usable depth of discharge
ηdis
Discharge efficiency (PCS + battery)
SoHEOL
State of health at end of warranty
  1. 01

    Log the load

    Twelve months of utility interval data, or two to four weeks of 15-minute logging on the main incomer.

  2. 02

    Set the target

    A peak cap in kW and a window in hours — or the critical load and ride-through time for backup.

  3. 03

    Size the power

    PCS rating ≥ peak to shave × 1.1, or critical load × 1.25 where motors create inrush.

  4. 04

    Size the energy

    Divide the energy to deliver by usable depth of discharge, discharge efficiency and end-of-life state of health.

  5. 05

    Check the site

    ~15 m² per MWh containerised, fire separation distances, plinth above flood level and warranty throughput.

Worked example

The load profile above, sized

350 kW / 1.4 MWh
Worked ESS sizing example
Peak to shave280 kW1,180 kW peak held to a 900 kW cap
Peak window17:00–22:005 hours above the cap
Energy to deliver1,030 kWhArea above the cap on the load profile
Usable depth of discharge90%
Discharge efficiency95%
End-of-life state of health90%Ageing allowance over the warranty
Nominal energy required1,339 kWh1,030 ÷ (0.90 × 0.95 × 0.90)
Selected system350 kW / 1.4 MWh5 × 280 kWh racks · ~21 m² containerised

Typical payback for peak-shaving and backup systems is 5–8 years, on capex or storage-as-a-service.

LFP rack · cell-level BMS

IEC 62619IEC 62933UL 9540ANFPA 855

Safety & thermal management

Five layers between a cell fault and your plant.

Heat is the enemy of every battery. Our systems are designed for 45 °C ambient, monsoon humidity and sites that flood.

  1. 01Cell

    Stable chemistry

    LFP cells certified to IEC 62619 and UL 1973, with no oxygen release in thermal abuse.

  2. 02Module

    Battery management

    Cell-level voltage and temperature monitoring with automatic contactor isolation.

  3. 03Rack

    Liquid cooling

    Coolant loop holds cell temperature within a narrow spread; HVAC sized for 45 °C ambient.

  4. 04Container

    Detection & suppression

    Off-gas and smoke detection, aerosol suppression and deflagration venting.

  5. 05Site

    Separation & siting

    Spacing per NFPA 855, UL 9540A test data, plinth above highest recorded flood level.

Monitoring integration

Every cell, visible from our control room.

Storage earns its payback only if it dispatches correctly every day. Your ESS joins the same 24/7 platform that watches our solar plants.

  • 01Live state of charge & healthSoC, SoH and cell temperature spread streamed to the EMS every second.
  • 02Alarms escalated 24/7Thermal, isolation and communication faults reach an engineer and your site team.
  • 03Monthly storage reportCycles, throughput, peak kW avoided and savings delivered against forecast.
  1. Battery racksBMS · cell data
    SoC · SoH
  2. Power conversionPCS · bi-directional
    Dispatch
  3. EMS controllerPeak & backup logic
    Telemetry
  4. Emerged NOC24/7 monitoring
Data path from cell to control room. EMS executes locally, so dispatch continues if the internet link drops.Battery dataControlRemote telemetry

Dhaka (Savar) · August 2025

Case study · ESS

400 kWp hybrid + 800 kWh ESS for a specialist hospital

Result
< 20 ms
switchover to battery
Sector
Healthcare & Education
Client
Specialist hospital

The challengeICU and imaging loads that cannot tolerate the 8–12 second genset start gap.

The resultNo critical-load interruption since commissioning and a 22% cut in evening peak demand charges.

FAQ

Storage questions, answered plainly

Lifespan, safety, retrofits and payback.

Ask an engineer

LFP systems are typically warranted for 10 years or 6,000 cycles to around 70–80% of original capacity, whichever comes first. With one cycle a day and good thermal control, 15 years of service is realistic.

LFP is the most thermally stable lithium chemistry in commercial use. Our containers add cell-level monitoring, liquid cooling, gas detection, suppression and deflagration venting, and are sited to NFPA 855 separation distances.

Yes. AC-coupled storage connects to your main switchboard alongside existing inverters. We check protection settings and export limits as part of the design.

Peak-shaving and backup systems typically pay back in 5–8 years, depending on your tariff category, how often you shed load and how much diesel the battery displaces.

It does. A battery can charge from the grid overnight and discharge in the evening peak, or sit ready as backup. Pairing with solar improves the economics further.

Free · no obligation

Send us your load data. We'll size the battery.

Share 12 months of bills or interval data and we'll return a sized ESS, a peak-shaving forecast and a payback period — in writing.

What you receive

  • 01Load-profile and peak analysis
  • 02Sized PCS and battery energy
  • 03Savings forecast and payback period